Convert between kilowatts, kVA, amps and horsepower for South African 230 V single-phase and 400 V three-phase supplies. Enter one value and the rest are worked out.

CT-03 · kW

Amps to kW Calculator

V

kW ↔ amps ↔ kVA ↔ hp for 230 V and 400 V, with power factor. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.

The formulas

  • Single-phase: I = P ÷ (V × PF), so 1 kW at 230 V and PF 1 is 4.35 A.
  • Three-phase: I = P ÷ (√3 × V × PF), so 1 kW at 400 V and PF 1 is 1.44 A per phase.
  • kVA is apparent power: kW ÷ PF. Generators, UPSs, inverters and transformers are rated in kVA.
  • Horsepower: 1 hp = 0.746 kW. Motor nameplates give output power; the electrical input is higher because of the motor's efficiency.

Which power factor to use

Use 1.0 for resistive loads: geysers, kettles, stoves, heaters and incandescent lights. Use about 0.8–0.85 for motors, pumps, compressors and air conditioners, and about 0.9–0.95 for modern LED drivers and electronics with power-factor correction. If you don't know, 0.8 is the usual planning figure and gives a slightly higher current.

From amps to cable size

The current tells you which breaker and cable the circuit needs. As a rough guide, a 3 kW geyser draws 13 A and goes on 2.5 mm² cable with a 20 A breaker; a 7.5 kW three-phase pump draws about 13.5 A per phase. Use the cable size calculator to allow for length, installation and voltage drop.

Frequently asked questions

How many amps is 1 kW?
About 4.35 A on a 230 V single-phase supply at power factor 1, and about 1.44 A per phase on a 400 V three-phase supply. With a power factor of 0.8 the current is 25% higher.
How many kW is 60 amps?
A 60 A single-phase supply at 230 V is 13.8 kVA, or about 13.8 kW for resistive loads. A 60 A three-phase supply at 400 V is about 41.6 kVA.
What size generator or inverter do I need?
Add up the kW of everything that must run at the same time, divide by the power factor to get kVA, and allow extra for motor starting currents. An electrician or solar installer can check the starting loads.