DC cable size for 12/24/48 V batteries, inverters and PV strings. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.
Why DC cable needs to be bigger
A 3 kW inverter on a 48 V battery bank draws about 63 A, and on 24 V it draws 125 A, against 13 A on the 230 V side. Voltage drop is a far bigger share of 12 V or 24 V than of 230 V, and a cable that drops a volt or two makes the inverter see a low battery and shut down early. Undersized battery cable also gets hot at the lugs. Most installers keep battery and inverter cables to 1–2% drop, and PV string cable to 1–3%.
The formula
For a two-wire DC circuit:
Cross-section (mm²) = 2 × length (m) × current (A) × ρ ÷ allowed drop (V)
where ρ is the resistivity of copper: 0.0172 Ω·mm²/m at 20 °C, or about 0.0206 at 70 °C. The calculator uses the warm figure, rounds up to the next standard size and then checks that the size can carry the current. For PV strings, enter the string's maximum-power voltage (Vmp) and current (Imp) from the panel datasheet.
Cable and protection
- Use solar PV cable (H1Z2Z2-K or equivalent, UV-resistant, 1–1.5 kV DC) between panels and the inverter or combiner.
- Use flexible battery or welding cable with crimped tinned-copper lugs between batteries and the inverter, and keep the runs short and equal in length.
- Fit a DC fuse or breaker rated for the battery's fault current close to the battery positive terminal.
Important: these results are estimates for planning and pricing. They use published IEC 60364-5-52 tables, the basis of SANS 10142-1, for copper or aluminium cable with PVC insulation, and do not cover every installation condition (thermal insulation, harmonics, fault-level and earth-loop checks). Fixed wiring in South Africa must be designed, installed and tested by a registered electrician, who issues the Certificate of Compliance (COC).
Frequently asked questions
What size cable for a 5 kW inverter on 48 V?
What size cable for solar panels?
Can I use house wire or surfix for DC?
Cable and services for this job
- EC-11Solar CableSingle-core 4 mm², 6 mm², 10 mm² and 16 mm² DC solar cable
- EC-12Battery CableSingle-core 16, 25, 35, 50, 70 and 95 mm²
- EC-13Welding CableSingle-core 16, 25, 35, 50, 70 and 95 mm²
- AC-04Cable Lugs and ConnectorsCopper, tinned copper, aluminium and bimetallic cable lugs
More calculators
- CT-01Cable Size CalculatorLoad, length and installation method in; recommended mm², breaker and voltage drop out.
- CT-02Voltage Drop CalculatorVolts lost, % of supply and maximum run length for any cable size.
- CT-03Amps to kW CalculatorkW ↔ amps ↔ kVA ↔ hp for 230 V and 400 V, with power factor.
- CT-05Conduit Fill CalculatorHow many house wires fit in 16–50 mm PVC conduit.
- CT-06Copper Weight CalculatorConductor kg per metre and total for any size, cores and length.
- CT-07Cable Size ChartCurrent ratings, mV/A/m, AWG equivalents and typical house circuits.