Load, length and installation method in; recommended mm², breaker and voltage drop out. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.
How to use the cable size calculator
Choose whether the load is in amps or kilowatts. For kW, also enter the power factor: 1 for heaters, geysers and stoves, around 0.8–0.85 for motors, pumps and air conditioners. Select single-phase (230 V) or three-phase (400 V), the one-way cable length in metres, and how the cable is installed. Add the ambient temperature and the number of circuits run together if they apply.
The result shows the recommended cable size, the breaker it is protected by, the derated current capacity and the voltage drop at the far end. The table under it compares the sizes either side, so you can see how close the next size down is.
How the size is worked out
The calculator follows the usual two checks a designer makes:
- Current capacity. It picks the smallest standard breaker at or above the load current, then the smallest cable whose rated current, multiplied by the temperature and grouping factors, is at least the breaker rating (Ib ≤ In ≤ Iz).
- Voltage drop. It multiplies the cable's mV/A/m figure by the load current and the length, and finds the smallest size that stays within your limit. SANS 10142-1 allows 5% of the supply voltage (11.5 V at 230 V), and many designers keep sub-mains to 2.5–3% so the final circuits still have room.
Whichever check needs the bigger cable sets the answer. On short runs it is usually current; on long runs to boreholes, gates, cottages and outbuildings it is almost always voltage drop.
Installation methods
How the cable is run changes how well it gets rid of heat. Cable in conduit in a wall (method B1) carries the least; surfix clipped to a wall or rafter (C) carries more; cable on open tray or ladder (E) carries the most. Cable in the ground (D) uses the ratings for cable in a sleeve or duct at 20 °C soil temperature, which is on the safe side for armoured cable buried directly. Cable buried in roof insulation or bunched in a ceiling void needs a further reduction that this tool doesn't apply.
Before you buy the cable
Important: these results are estimates for planning and pricing. They use published IEC 60364-5-52 tables, the basis of SANS 10142-1, for copper or aluminium cable with PVC insulation, and do not cover every installation condition (thermal insulation, harmonics, fault-level and earth-loop checks). Fixed wiring in South Africa must be designed, installed and tested by a registered electrician, who issues the Certificate of Compliance (COC).
Once you know the size, list the cable type, number of cores, length and installation in a quote request and a supplier or electrical contractor will price it.
Frequently asked questions
What size cable do I need for 60 amps?
What size cable for a 32 A circuit?
Does the calculator work for armoured cable?
Why is aluminium cable bigger than copper for the same load?
Cable and services for this job
- SV-07Cable Size Guide1.5 mm² lights, 2.5 mm² plugs
- EC-05Armoured Cable (SWA)PVC/SWA/PVC or XLPE/SWA/PVC, 600/1000 V
- EC-032.5mm Electrical Cable2.5 mm² conductor, plain annealed copper
- EC-0416mm Electrical Cable16 mm² copper or aluminium conductors
More calculators
- CT-02Voltage Drop CalculatorVolts lost, % of supply and maximum run length for any cable size.
- CT-03Amps to kW CalculatorkW ↔ amps ↔ kVA ↔ hp for 230 V and 400 V, with power factor.
- CT-04Solar & Battery Cable CalculatorDC cable size for 12/24/48 V batteries, inverters and PV strings.
- CT-05Conduit Fill CalculatorHow many house wires fit in 16–50 mm PVC conduit.
- CT-06Copper Weight CalculatorConductor kg per metre and total for any size, cores and length.
- CT-07Cable Size ChartCurrent ratings, mV/A/m, AWG equivalents and typical house circuits.