Enter the load, the cable length and how the cable is installed. The calculator picks the smallest copper or aluminium cable that carries the current after derating and keeps voltage drop within the limit.

CT-01 · mm²

Cable Size Calculator

A
m
°C

Load, length and installation method in; recommended mm², breaker and voltage drop out. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.

How to use the cable size calculator

Choose whether the load is in amps or kilowatts. For kW, also enter the power factor: 1 for heaters, geysers and stoves, around 0.8–0.85 for motors, pumps and air conditioners. Select single-phase (230 V) or three-phase (400 V), the one-way cable length in metres, and how the cable is installed. Add the ambient temperature and the number of circuits run together if they apply.

The result shows the recommended cable size, the breaker it is protected by, the derated current capacity and the voltage drop at the far end. The table under it compares the sizes either side, so you can see how close the next size down is.

How the size is worked out

The calculator follows the usual two checks a designer makes:

  • Current capacity. It picks the smallest standard breaker at or above the load current, then the smallest cable whose rated current, multiplied by the temperature and grouping factors, is at least the breaker rating (Ib ≤ In ≤ Iz).
  • Voltage drop. It multiplies the cable's mV/A/m figure by the load current and the length, and finds the smallest size that stays within your limit. SANS 10142-1 allows 5% of the supply voltage (11.5 V at 230 V), and many designers keep sub-mains to 2.5–3% so the final circuits still have room.

Whichever check needs the bigger cable sets the answer. On short runs it is usually current; on long runs to boreholes, gates, cottages and outbuildings it is almost always voltage drop.

Installation methods

How the cable is run changes how well it gets rid of heat. Cable in conduit in a wall (method B1) carries the least; surfix clipped to a wall or rafter (C) carries more; cable on open tray or ladder (E) carries the most. Cable in the ground (D) uses the ratings for cable in a sleeve or duct at 20 °C soil temperature, which is on the safe side for armoured cable buried directly. Cable buried in roof insulation or bunched in a ceiling void needs a further reduction that this tool doesn't apply.

Before you buy the cable

Important: these results are estimates for planning and pricing. They use published IEC 60364-5-52 tables, the basis of SANS 10142-1, for copper or aluminium cable with PVC insulation, and do not cover every installation condition (thermal insulation, harmonics, fault-level and earth-loop checks). Fixed wiring in South Africa must be designed, installed and tested by a registered electrician, who issues the Certificate of Compliance (COC).

Once you know the size, list the cable type, number of cores, length and installation in a quote request and a supplier or electrical contractor will price it.

Frequently asked questions

What size cable do I need for 60 amps?
16 mm² copper is the usual size for a 60 A single-phase supply. It stays within the 5% voltage drop limit up to about 65 m at full load; if you keep the supply cable to 2.5% so the circuits after it have room, 25 mm² is needed beyond about 35 m. Enter your length in the calculator to check.
What size cable for a 32 A circuit?
4 mm² copper is rated 32–36 A and is used for short 32 A runs. Electricians often choose 6 mm² when the cable is grouped with other circuits, runs through insulation, or is longer than about 30 m, where 4 mm² goes over the 5% voltage drop limit.
Does the calculator work for armoured cable?
Yes. Choose 'Buried in the ground' for armoured cable underground, or 'On cable tray' if it is run on tray. PVC armoured cable (SWA) uses the same conductor ratings as other PVC-insulated cable.
Why is aluminium cable bigger than copper for the same load?
Aluminium has about 1.6 times the resistance of copper, so it needs roughly one and a half sizes larger for the same current and voltage drop. It is lighter and cheaper, and is normally only used from 16 mm² upwards.