Cable Size Chart and Current Ratings

Current ratings, voltage drop figures and AWG equivalents for copper cable from 1.5 mm² to 300 mm², plus the sizes South African electricians usually use for each circuit in a home.

CT-07 · A/mm²

Jump to a table

All values for copper PVC cable unless stated. Planning figures; confirm with the manufacturer's datasheet and your electrician.

A quick reference for choosing cable. The ratings are starting points before derating; for a specific circuit use the cable size calculator and the voltage drop calculator.

Current ratings of copper PVC cable

Current-carrying capacity in amps for copper conductors with PVC insulation (70 °C), from IEC 60364-5-52, which SANS 10142-1 is based on. 1-ph is two loaded conductors (single-phase); 3-ph is three loaded conductors. Air ratings are at 30 °C ambient, ground ratings at 20 °C soil.

B1: In conduit or trunking (house wire in walls) · C: Clipped to a wall or in a roof space (surfix) · E: On cable tray or ladder, in free air · D: Buried in the ground (direct or in a sleeve)

SizeB1CED
1-ph3-ph1-ph3-ph1-ph3-ph1-ph3-ph
1.5 mm²17.515.519.517.52218.52218
2.5 mm²2421272430252924
4 mm²3228363240343730
6 mm²4136464151434638
10 mm²5750635770606050
16 mm²7668857694807864
25 mm²10189112961191019982
35 mm²12511013811914812611998
50 mm²151134168144180153140116
70 mm²192171213184232196173143
95 mm²232207258223282238204169
120 mm²269239299259328276231192
150 mm²––344299379319261217
185 mm²––392341434364292243
240 mm²––461403514430336280
300 mm²––530464593497379316

Multiply by the temperature and grouping factors where they apply, for example 0.87 at 40 °C ambient or 0.70 for three circuits bunched in one conduit. The cable size calculator does this for you.

Voltage drop and AWG equivalents

Voltage drop in millivolts per amp per metre (mV/A/m) for copper PVC cable at operating temperature, and the nearest American Wire Gauge size. Multiply the mV/A/m by the current and the one-way length, then divide by 1000 for volts.

SizemV/A/m 1-phmV/A/m 3-phNearest AWG / kcmil
1.5 mm²28.92516 AWG (1.31 mm²)
2.5 mm²17.31514 AWG (2.08 mm²)
4 mm²11.09.512 AWG (3.31 mm²)
6 mm²7.46.410 AWG (5.26 mm²)
10 mm²4.43.88 AWG (8.37 mm²)
16 mm²2.82.46 AWG (13.3 mm²)
25 mm²1.71.54 AWG (21.2 mm²)
35 mm²1.31.12 AWG (33.6 mm²)
50 mm²0.940.811/0 AWG (53.5 mm²)
70 mm²0.660.572/0 AWG (67.4 mm²)
95 mm²0.480.423/0 AWG (85.0 mm²)
120 mm²0.400.354/0 AWG (107 mm²)
150 mm²0.330.29300 kcmil (152 mm²)
185 mm²0.280.24350 kcmil (177 mm²)
240 mm²0.240.21500 kcmil (253 mm²)
300 mm²0.210.185600 kcmil (304 mm²)

Typical cable sizes for a South African home

CircuitCableBreakerNotes
Lights1.5 mm²10 ASurfix or house wire in conduit
Plugs (socket outlets)2.5 mm²20 ARing or radial; long runs may need 4 mm²
Geyser (2–4 kW)2.5 mm²20 AIsolator next to the geyser
Air conditioner (up to 18 000 BTU)2.5 mm²20 ADedicated circuit with isolator
Stove or oven4–6 mm²32–40 ASize from the appliance rating
Pool or borehole pump2.5–4 mm²16–20 AArmoured cable underground; check voltage drop
Gate motor1.5–2.5 mm²10 AArmoured cable; long driveways need a size up
Sub-DB to a cottage or garage6–10 mm²32–50 AArmoured cable; size for load and length
Main supply, 60 A single-phase16 mm²60 AMunicipal or Eskom service connection
Main supply, 80 A three-phase25 mm² 4-core80 AArmoured cable from the meter kiosk

These are the usual sizes on short runs. Long runs, grouped circuits and hot roof spaces can all need the next size up, and the electrician who issues your COC has the final say.

Aluminium cable

Aluminium conductors carry about 78% of the current of the same copper size and have about 1.6 times the voltage drop, so they are typically one or two sizes larger. They are much lighter and cheaper, which is why municipal and large supply cables from 16 mm² up are often aluminium. Aluminium needs bi-metal lugs and correctly torqued terminations.

Frequently asked questions

How many amps can 2.5 mm² cable carry?
About 24 A in conduit and 27 A clipped direct for a single-phase circuit, before derating. In South Africa 2.5 mm² plug circuits are normally protected by a 20 A breaker.
How many amps can 16 mm² cable carry?
About 76 A in conduit, 85 A clipped direct and 78 A in the ground for a single-phase circuit. It is the common size for a 60 A household supply.
What is 2.5 mm² in AWG?
2.5 mm² sits between 14 AWG (2.08 mm²) and 13 AWG (2.63 mm²). It is usually compared with 14 AWG.