A quick reference for choosing cable. The ratings are starting points before derating; for a specific circuit use the cable size calculator and the voltage drop calculator.
Current ratings of copper PVC cable
Current-carrying capacity in amps for copper conductors with PVC insulation (70 °C), from IEC 60364-5-52, which SANS 10142-1 is based on. 1-ph is two loaded conductors (single-phase); 3-ph is three loaded conductors. Air ratings are at 30 °C ambient, ground ratings at 20 °C soil.
B1: In conduit or trunking (house wire in walls) · C: Clipped to a wall or in a roof space (surfix) · E: On cable tray or ladder, in free air · D: Buried in the ground (direct or in a sleeve)
| Size | B1 | C | E | D | ||||
|---|---|---|---|---|---|---|---|---|
| 1-ph | 3-ph | 1-ph | 3-ph | 1-ph | 3-ph | 1-ph | 3-ph | |
| 1.5 mm² | 17.5 | 15.5 | 19.5 | 17.5 | 22 | 18.5 | 22 | 18 |
| 2.5 mm² | 24 | 21 | 27 | 24 | 30 | 25 | 29 | 24 |
| 4 mm² | 32 | 28 | 36 | 32 | 40 | 34 | 37 | 30 |
| 6 mm² | 41 | 36 | 46 | 41 | 51 | 43 | 46 | 38 |
| 10 mm² | 57 | 50 | 63 | 57 | 70 | 60 | 60 | 50 |
| 16 mm² | 76 | 68 | 85 | 76 | 94 | 80 | 78 | 64 |
| 25 mm² | 101 | 89 | 112 | 96 | 119 | 101 | 99 | 82 |
| 35 mm² | 125 | 110 | 138 | 119 | 148 | 126 | 119 | 98 |
| 50 mm² | 151 | 134 | 168 | 144 | 180 | 153 | 140 | 116 |
| 70 mm² | 192 | 171 | 213 | 184 | 232 | 196 | 173 | 143 |
| 95 mm² | 232 | 207 | 258 | 223 | 282 | 238 | 204 | 169 |
| 120 mm² | 269 | 239 | 299 | 259 | 328 | 276 | 231 | 192 |
| 150 mm² | – | – | 344 | 299 | 379 | 319 | 261 | 217 |
| 185 mm² | – | – | 392 | 341 | 434 | 364 | 292 | 243 |
| 240 mm² | – | – | 461 | 403 | 514 | 430 | 336 | 280 |
| 300 mm² | – | – | 530 | 464 | 593 | 497 | 379 | 316 |
Multiply by the temperature and grouping factors where they apply, for example 0.87 at 40 °C ambient or 0.70 for three circuits bunched in one conduit. The cable size calculator does this for you.
Voltage drop and AWG equivalents
Voltage drop in millivolts per amp per metre (mV/A/m) for copper PVC cable at operating temperature, and the nearest American Wire Gauge size. Multiply the mV/A/m by the current and the one-way length, then divide by 1000 for volts.
| Size | mV/A/m 1-ph | mV/A/m 3-ph | Nearest AWG / kcmil |
|---|---|---|---|
| 1.5 mm² | 28.9 | 25 | 16 AWG (1.31 mm²) |
| 2.5 mm² | 17.3 | 15 | 14 AWG (2.08 mm²) |
| 4 mm² | 11.0 | 9.5 | 12 AWG (3.31 mm²) |
| 6 mm² | 7.4 | 6.4 | 10 AWG (5.26 mm²) |
| 10 mm² | 4.4 | 3.8 | 8 AWG (8.37 mm²) |
| 16 mm² | 2.8 | 2.4 | 6 AWG (13.3 mm²) |
| 25 mm² | 1.7 | 1.5 | 4 AWG (21.2 mm²) |
| 35 mm² | 1.3 | 1.1 | 2 AWG (33.6 mm²) |
| 50 mm² | 0.94 | 0.81 | 1/0 AWG (53.5 mm²) |
| 70 mm² | 0.66 | 0.57 | 2/0 AWG (67.4 mm²) |
| 95 mm² | 0.48 | 0.42 | 3/0 AWG (85.0 mm²) |
| 120 mm² | 0.40 | 0.35 | 4/0 AWG (107 mm²) |
| 150 mm² | 0.33 | 0.29 | 300 kcmil (152 mm²) |
| 185 mm² | 0.28 | 0.24 | 350 kcmil (177 mm²) |
| 240 mm² | 0.24 | 0.21 | 500 kcmil (253 mm²) |
| 300 mm² | 0.21 | 0.185 | 600 kcmil (304 mm²) |
Typical cable sizes for a South African home
| Circuit | Cable | Breaker | Notes |
|---|---|---|---|
| Lights | 1.5 mm² | 10 A | Surfix or house wire in conduit |
| Plugs (socket outlets) | 2.5 mm² | 20 A | Ring or radial; long runs may need 4 mm² |
| Geyser (2–4 kW) | 2.5 mm² | 20 A | Isolator next to the geyser |
| Air conditioner (up to 18 000 BTU) | 2.5 mm² | 20 A | Dedicated circuit with isolator |
| Stove or oven | 4–6 mm² | 32–40 A | Size from the appliance rating |
| Pool or borehole pump | 2.5–4 mm² | 16–20 A | Armoured cable underground; check voltage drop |
| Gate motor | 1.5–2.5 mm² | 10 A | Armoured cable; long driveways need a size up |
| Sub-DB to a cottage or garage | 6–10 mm² | 32–50 A | Armoured cable; size for load and length |
| Main supply, 60 A single-phase | 16 mm² | 60 A | Municipal or Eskom service connection |
| Main supply, 80 A three-phase | 25 mm² 4-core | 80 A | Armoured cable from the meter kiosk |
These are the usual sizes on short runs. Long runs, grouped circuits and hot roof spaces can all need the next size up, and the electrician who issues your COC has the final say.
Aluminium cable
Aluminium conductors carry about 78% of the current of the same copper size and have about 1.6 times the voltage drop, so they are typically one or two sizes larger. They are much lighter and cheaper, which is why municipal and large supply cables from 16 mm² up are often aluminium. Aluminium needs bi-metal lugs and correctly torqued terminations.
Frequently asked questions
How many amps can 2.5 mm² cable carry?
How many amps can 16 mm² cable carry?
What is 2.5 mm² in AWG?
Cable and services for this job
- SV-07Cable Size Guide1.5 mm² lights, 2.5 mm² plugs
- EC-032.5mm Electrical Cable2.5 mm² conductor, plain annealed copper
- EC-0416mm Electrical Cable16 mm² copper or aluminium conductors
- EC-08House Wire1.5, 2.5, 4, 6, 10 and 16 mm² copper conductors
More calculators
- CT-01Cable Size CalculatorLoad, length and installation method in; recommended mm², breaker and voltage drop out.
- CT-02Voltage Drop CalculatorVolts lost, % of supply and maximum run length for any cable size.
- CT-03Amps to kW CalculatorkW ↔ amps ↔ kVA ↔ hp for 230 V and 400 V, with power factor.
- CT-04Solar & Battery Cable CalculatorDC cable size for 12/24/48 V batteries, inverters and PV strings.
- CT-05Conduit Fill CalculatorHow many house wires fit in 16–50 mm PVC conduit.
- CT-06Copper Weight CalculatorConductor kg per metre and total for any size, cores and length.