CT-02 · Calculator

Voltage Drop Calculator

Check whether a cable size is big enough for a long run. Enter the size, length and load current to see the volts lost, the percentage of the supply voltage and how far the cable can go.

CT-02 · ΔV

Voltage Drop Calculator

A
m

Volts lost, % of supply and maximum run length for any cable size. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.

Why voltage drop matters

Every metre of cable has resistance, so some voltage is lost between the DB and the load. Too much drop makes motors run hot and struggle to start, makes lights dim and stops inverters, chargers and electronics from working properly. It also wastes energy as heat in the cable. SANS 10142-1 limits the drop from the point of supply to any point in the installation to 5% of the nominal voltage: 11.5 V on a 230 V supply or 20 V on a 400 V three-phase supply.

The formula

Cable manufacturers publish a voltage drop figure in millivolts per amp per metre (mV/A/m) for each size. The drop is:

Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1000

The length is the one-way route length; the figure already allows for the current flowing out and back. Three-phase figures are lower than single-phase because the load is shared between three phases. The calculator uses figures for copper PVC cable at its full operating temperature, with aluminium about 1.6 times higher, so the answer is on the conservative side for lightly loaded cable.

Typical long runs

  • Borehole pump 120 m away: a 2.2 kW single-phase pump draws about 12 A. On 2.5 mm² the drop is about 25 V (11%); 6 mm² brings it to about 10.6 V (4.6%).
  • Cottage sub-DB 60 m away at 40 A: 10 mm² drops about 10.5 V (4.6%), so 16 mm² is the safer choice if lights and plugs are added after it.
  • Gate motor 80 m from the house: small current, but the starting surge makes 2.5 mm² the practical minimum.

Next steps

Important: these results are estimates for planning and pricing. They use published IEC 60364-5-52 tables, the basis of SANS 10142-1, for copper or aluminium cable with PVC insulation, and do not cover every installation condition (thermal insulation, harmonics, fault-level and earth-loop checks). Fixed wiring in South Africa must be designed, installed and tested by a registered electrician, who issues the Certificate of Compliance (COC).

Need the cable? Put the size, cores and length in a quote request and a supplier or contractor near you will quote.

Frequently asked questions

What is the maximum voltage drop allowed in South Africa?
SANS 10142-1 allows 5% of the nominal supply voltage from the point of supply to the furthest point of the installation: 11.5 V at 230 V single-phase and 20 V at 400 V three-phase. Designers often keep the main and sub-main cables to about 2.5% so final circuits have room.
Is the cable length one way or both ways?
One way. Enter the route length from the DB to the load; the mV/A/m figures already include the return conductor.
How do I reduce voltage drop?
Use a larger conductor, shorten the route, or change from single-phase to three-phase for large loads. Going up one cable size typically cuts the drop by a third or more.