Volts lost, % of supply and maximum run length for any cable size. Free to use, no sign-up. When you know what you need, send a quote request and a cable supplier or electrical contractor near you will price it.
Why voltage drop matters
Every metre of cable has resistance, so some voltage is lost between the DB and the load. Too much drop makes motors run hot and struggle to start, makes lights dim and stops inverters, chargers and electronics from working properly. It also wastes energy as heat in the cable. SANS 10142-1 limits the drop from the point of supply to any point in the installation to 5% of the nominal voltage: 11.5 V on a 230 V supply or 20 V on a 400 V three-phase supply.
The formula
Cable manufacturers publish a voltage drop figure in millivolts per amp per metre (mV/A/m) for each size. The drop is:
Voltage drop (V) = mV/A/m × current (A) × length (m) ÷ 1000
The length is the one-way route length; the figure already allows for the current flowing out and back. Three-phase figures are lower than single-phase because the load is shared between three phases. The calculator uses figures for copper PVC cable at its full operating temperature, with aluminium about 1.6 times higher, so the answer is on the conservative side for lightly loaded cable.
Typical long runs
- Borehole pump 120 m away: a 2.2 kW single-phase pump draws about 12 A. On 2.5 mm² the drop is about 25 V (11%); 6 mm² brings it to about 10.6 V (4.6%).
- Cottage sub-DB 60 m away at 40 A: 10 mm² drops about 10.5 V (4.6%), so 16 mm² is the safer choice if lights and plugs are added after it.
- Gate motor 80 m from the house: small current, but the starting surge makes 2.5 mm² the practical minimum.
Next steps
Important: these results are estimates for planning and pricing. They use published IEC 60364-5-52 tables, the basis of SANS 10142-1, for copper or aluminium cable with PVC insulation, and do not cover every installation condition (thermal insulation, harmonics, fault-level and earth-loop checks). Fixed wiring in South Africa must be designed, installed and tested by a registered electrician, who issues the Certificate of Compliance (COC).
Need the cable? Put the size, cores and length in a quote request and a supplier or contractor near you will quote.
Frequently asked questions
What is the maximum voltage drop allowed in South Africa?
Is the cable length one way or both ways?
How do I reduce voltage drop?
Cable and services for this job
- SV-07Cable Size Guide1.5 mm² lights, 2.5 mm² plugs
- SV-02Underground Cable InstallationSteel wire armoured cable from 2.5 mm² to large multi-core sizes
- EC-05Armoured Cable (SWA)PVC/SWA/PVC or XLPE/SWA/PVC, 600/1000 V
- EC-14Copper and Aluminium CableCopper conductors from 1.5 mm² upward for wiring and feeders
More calculators
- CT-01Cable Size CalculatorLoad, length and installation method in; recommended mm², breaker and voltage drop out.
- CT-03Amps to kW CalculatorkW ↔ amps ↔ kVA ↔ hp for 230 V and 400 V, with power factor.
- CT-04Solar & Battery Cable CalculatorDC cable size for 12/24/48 V batteries, inverters and PV strings.
- CT-05Conduit Fill CalculatorHow many house wires fit in 16–50 mm PVC conduit.
- CT-06Copper Weight CalculatorConductor kg per metre and total for any size, cores and length.
- CT-07Cable Size ChartCurrent ratings, mV/A/m, AWG equivalents and typical house circuits.